FN9290B-10-06

Schaffner IEC filter FN 9290 Panel mounting 250V 10A Medical IP40

Manufacturer Part No.
FN9290B-10-06
Schukat Part No.
FN9290B-10-06
Manufacturer
Enter your company's part number here. Your part number will be referenced on your receipts, such as the order confirmation, invoice or delivery note.
Enter your personal project number here to assign the item to a project. Your part project number will be referenced on your receipts, such as the order confirmation, invoice or delivery note.

0 Pcs. in stock

Planned delivery time
Ø 16 Weeks
Life Cycle Status
The life cycle indicates which market phase the item is in. We distinguish between: • Active (green) • NRND = Not Recommended for New Designs (yellow) • LTB = Last Time Buy (yellow) • EOL = End of Life (red)
Active
Available on order
Replacement / Follow-up View entire series
Data Sheet
ECAD Model
Downloads

Prices

Manufacturer bundle 40 Pcs.
Manufacturer's packaging unit (Mfr. PU) means the smallest original packaging unit of the manufacturer.
Price per 1 Pcs.

Quantity and Options

(at least 40 or multiple of 40)
All prices net plus VAT. We do not deliver to private customers.

Fact Sheet

Series
FN 9290
Type
IEC filter
Rated voltage at 50/60Hz
250 V
Rated current
10 A
Approvals
CE
CQC
ENEC14
UK CA
UL
cCSA
Protection class front side
IP40
RoHS-Conform

Specifications

Open all

General

Manufacturer
  • Schaffner
Series
  • FN 9290
Product group
  • D3291 IEC FILTER FN9290
Application
  • Medical
Type
  • IEC filter
Assembly Type
  • Panel mounting
Features
  • - Filter built in a metal housing with integrated power line connector, fuse holder and 2-pole, non-illuminated line switch
    - Fuse holder for two fuses 5x20mm
    - With flat plug connection 6.3x0.8mm
     

Dimensions and weights

Dimension: Length
  • 74.8 mm
Dimension: Width
  • 46.2 mm
Dimension: Height
  • 49.8 mm

Operating conditions

Operating Temperature Min.
  • -25 °C
Operating Temperature Max.
  • 85 °C

Technical features

Rated voltage at 50/60Hz
  • 250 V
Dielectric strength, 2s, conductor/earth
  • 2,5 kV AC
Dielectric strength, 2s, conductor/conductor
  • 0,76 kV AC
Rated current
  • 10 A
Inductance
  • 0.32 mH
Cx
  • 220 nF

Safety/Certifications

Approvals
  • CE
  • CQC
  • ENEC14
  • UK CA
  • UL
  • cCSA
Protection class front side
  • IP40
Standards
  • UL 1283; CSA 22.2 No. 8 1986; EN 60939; EN 60950; EN 60601-1; UL 544; EN 60320