RACM600-24SL/OF

Recom AC/DC industrial power supply unit Open Frame 600W 24V 25A PM-Bus 2*MOPP

RACM600-24SL/OFRACM600-24SL/OF
Manufacturer Part No.
RACM600-24SL/OF
Schukat Part No.
RACM600-24SL/OF
Manufacturer
Enter your company's part number here. Your part number will be referenced on your receipts, such as the order confirmation, invoice or delivery note.
Enter your personal project number here to assign the item to a project. Your part project number will be referenced on your receipts, such as the order confirmation, invoice or delivery note.

7 Pcs. in stock

Planned delivery time
Ø 39 Weeks
Life Cycle Status
The life cycle indicates which market phase the item is in. We distinguish between: • Active (green) • NRND = Not Recommended for New Designs (yellow) • LTB = Last Time Buy (yellow) • EOL = End of Life (red)
Active
Available (from stock)
Replacement / Follow-up View entire series
Data Sheet
ECAD Model
Downloads

Prices

Manufacturer bundle 7 Pcs.
Manufacturer's packaging unit (Mfr. PU) means the smallest original packaging unit of the manufacturer.
Price per 1 Pcs.

Quantity and Options

(at least 1 or multiple of 1)
All prices net plus VAT. We do not deliver to private customers.

Fact Sheet

Package/Case
Open Frame
Output Power
600 W
Output voltage
24 V
Output current
25.000 A
Efficiency
93 %
Medical protection classification
2*MOPP
RoHS-Conform

Specifications

Open all

General

Manufacturer
  • Recom
Series
  • RACM600-L
Product group
  • M3530
Application
  • ITE
  • Industry
  • Medical
Package/Case
  • Open Frame
Dimension: Length
  • 196.8 mm
Dimension: Width
  • 101.6 mm
Dimension: Height
  • 40.6 mm
Weight
  • 1,000 g
Interfaces
  • PM-Bus
Manufacturer's warranty (years)
  • 3
Product description
  • RACM600-L/OF Series AC/DC power supply units are designed to support operation in natural convection where conduction cooling is not an option for up to 450W continuous and peak power of up to 400W or 600W. Safety approvals to Medical IEC 60601-1-2, to IT and to industrial IEC 62368 standards and operations with worldwide input voltage conditions from 80 to 275VAC in altitudes of up to 5.000m makes these chassis mount units ideal for global use in various automation processes. For enhanced reliability requirements of applications, redundant operation is supported with active current sharing. An additional 5V “always on” Stand by output powers housekeeping circuitry to control remote on/off and monitoring functions, which are available via the PMBus I²C interface. EN55032 class B coverage is given without any external components, which underlines the versatility of these power supplies.
Features
  • AUX Power Supply
  • Adjustable Output Voltage
  • DC compatible
  • DC-OK-Signal
  • Parallel Function
  • Peak Power
  • Remote Function
  • Remote Sense
Application note
  • These power supplies are considered as a component that has to be installed in a final equipment.

Operating conditions

MTBF
  • 500,000 h
Operating Temperature Min.
  • -20 °C
Operating Temperature Max.
  • 70 °C
Storage Temperature Min.
  • -40 °C
Storage Temperature Max.
  • 85 °C

Input

Mains connection/phases
  • I
Mains frequency min.
  • 47 Hz
Mains frequency max.
  • 63 Hz
Input voltage min. AC
  • 80 V
Input voltage max. AC
  • 275 V
Input voltage min. DC
  • 120 V
Input voltage max. DC
  • 300 V
Efficiency
  • 93 %
Leakage current, max.
  • 0.3 mA
Inrush current, max.
  • 20 A
Power factor correction (PFC)
Power factor
  • 0.9
Connection type, input
  • Screw Terminal

Output

Number of outputs
  • 1
Output Power
  • 600 W
Output power convection cooled
  • 450 W
Output voltage
  • 24 V
Output voltage tolerance
  • -225.225 %
Output current
  • 25.000 A
Overload protection
Short-circuit protection
Overvoltage protection
Overtemperature protection
Connection type, output
  • Screw Terminal

Safety/Certifications

Protection class
  • I
Isolation voltage I/P-O/P
  • 4,000 V
Isolation voltage I/P-FG
  • 1,500 V
Isolation voltage O/P-FG
  • 1,500 V
Approvals
  • CE
  • CSA
  • EN
  • IEC
  • UKCA
  • UL
Standards (EMC)
  • EN 55032
  • EN 55032 Class B
  • EN 60601-1-2
Standards (safety)
  • ANSI/AAMI ES 60601-1
  • EN 60601-1
  • EN 62368-1
  • IEC 60601-1
  • IEC 62368-1
  • UL 62368-1
Medical protection classification
  • 2*MOPP

Documents